Collect industrial data from OPC UA
Read process values from an OPC UA server, such as a PLC, historian, or SCADA gateway, and write them to InfluxDB 3. OPC UA is the standard interface for industrial equipment, and this pattern is the foundation of most IIoT monitoring pipelines.
There are two ways to tell Telegraf which nodes to read:
- Discover nodes with browse patterns (Telegraf 1.39+, recommended): Telegraf walks the server’s address space and matches nodes against glob patterns.
- Define nodes explicitly (all versions): you list every node to read.
If your address space is large or changes over time, we recommend upgrading to Telegraf 1.39 or later and using browse-based discovery.
Discover nodes with browse patterns
Instead of enumerating every node, describe them with patterns. Telegraf browses the server’s address space, matches Variable nodes against each pattern, and reads everything that matches:
[[inputs.opcua]]
## OPC UA server endpoint.
endpoint = "opc.tcp://plc-gateway.factory.local:4840"
connect_timeout = "10s"
request_timeout = "5s"
## Security settings negotiated with the server.
security_policy = "Basic256Sha256"
security_mode = "SignAndEncrypt"
auth_method = "UserName"
username = "telegraf"
password = "example-password"
## Use the timestamp reported by the data source.
timestamp = "source"
[inputs.opcua.browse]
## Optional safety limits for the browse walk.
depth = 10
max_nodes = 50000
## Read every motor valve on every line in Plant1.
[[inputs.opcua.browse.paths]]
pattern = "Plant1/*/MV*"
name = "motor_valves"
default_tags = { plant = "plant1" }
## Read every temperature node, wherever it lives.
[[inputs.opcua.browse.paths]]
pattern = "**/Temperature"
name = "temperatures"
[[outputs.influxdb_v3]]
urls = ["http://localhost:8181"]
token = "AUTH_TOKEN"
database = "DATABASE_NAME"Replace the following:
AUTH_TOKEN: your InfluxDB authorization tokenDATABASE_NAME: the database to write to
How discovery works
- Patterns match against browse paths with
/as the segment separator:*matches one segment or characters within a segment,**matches any number of segments, and?,[abc], and{a,b}match within a segment. - Each
pathsrule becomes a metric group: the rule’snameis the measurement name and itsdefault_tagsapply to every matched node. A node matching multiple patterns appears in each group. - Discovery repeats on every connect, so nodes added to or removed from the server are picked up on reconnect without restarting Telegraf or editing the configuration.
depthandmax_nodesbound the walk on large address spaces, androotstarts the walk somewhere other than the standard Objects folder (node-ID form, for exampleroot = "ns=0;i=85").- Browse-based discovery is backward compatible: explicit
nodesandgroupentries keep working alongside it.
Define nodes explicitly
On Telegraf versions earlier than 1.39, or when you want exact control
over what’s read and how fields are named, list each node.
Replace the [inputs.opcua.browse] section with group and nodes
definitions:
## Machine-state nodes, grouped so they share a measurement name
## and tags.
[[inputs.opcua.group]]
name = "press_line"
namespace = "3"
identifier_type = "s"
default_tags = { line = "assembly-2" }
nodes = [
{name="temperature", identifier="Press04.Temperature"},
{name="pressure", identifier="Press04.Pressure"},
{name="cycle_count", identifier="Press04.CycleCount"},
]- The
grouptable sets shared properties for its nodes: thepress_linemeasurement name, the OPC UA namespace, the identifier type (sfor string identifiers), and alinetag applied to every node. nodeslists the values to read. Each node’snamebecomes the field key, andidentifieris the node ID as shown in your OPC UA browser, combining with the group’s namespace to form IDs likens=3;s=Press04.Temperature.- Add one
[[inputs.opcua.group]]per machine or line, each with its own measurement name and default tags.
Connection and security
These settings apply to both methods:
endpointis the OPC UA server address. The security policy, mode, and authentication method must match what the server allows. Setsecurity_policy = "auto"andsecurity_mode = "auto"to negotiate automatically. If certificate files aren’t specified, Telegraf creates a self-signed client certificate, which most servers require you to trust before reads succeed.timestamp = "source"uses the timestamp attached to each value by the data source instead of the collection time, preserving the true observation time of each reading.- On each collection interval, Telegraf reads all configured or
discovered nodes and emits one metric per node, with the node ID as an
idtag and the OPC UA status in aQualityfield.
Example output
From the explicit configuration above:
press_line,id=ns\=3;s\=Press04.Temperature,line=assembly-2 temperature=76.2,Quality="OK (0x0)" 1709572232000000000
press_line,id=ns\=3;s\=Press04.Pressure,line=assembly-2 pressure=101.4,Quality="OK (0x0)" 1709572232000000000
press_line,id=ns\=3;s\=Press04.CycleCount,line=assembly-2 cycle_count=18342i,Quality="OK (0x0)" 1709572232000000000With browse-based discovery, each metric uses its rule’s name as the
measurement name and the node’s browse name as the field key, for example
motor_valves metrics tagged plant=plant1.
Extend this example
- For servers that support subscriptions, the opcua_listener input receives value changes as they happen instead of polling. It supports the same browse-based discovery in Telegraf 1.39+.
- For devices that speak Modbus instead of OPC UA, the modbus input reads holding registers, coils, and inputs directly. Equipment publishing MQTT can use the MQTT example pattern.
- To reduce write volume from fast-changing values, downsample before writing. See Downsample metrics before writing.